Basic Information
Manufacturer: MTL Instruments (Eaton)
Product Family: MTL4000 Series
Function: 1-Channel Isolated Barrier & Repeater for 2/3-Wire Transmitters
Key Feature: HART® / Digital Communication Transparency (Bi-Directional)
Product Description
The MTL4041B provides a fully floating dc supply for energising a conventional 2- or 3-wire 4/20mA transmitter or a ‘smart’ transmitter located in a hazardous area, and repeats the current in another circuit to drive a safe-area load. For smart transmitters, the unit allows bi-directional transmission of digital communication signals superimposed on the 4/20mA signal so that the transmitter can be interrogated either from the operator station or by a hand-held communicator (HHC). The module can also be used with hazardousarea current sources and some vortex and turbine meters.
Technical Specifications
|
Section |
Parameter (English) |
Specification / Value |
|
General |
Number of Channels |
1 |
|
|
Transmitter Type |
2-Wire, 3-Wire, Smart (HART®), Current Sources |
|
|
Hazardous Area Location |
Zone 0, IIC, T4-6 / Div. 1, Group A |
|
Field Power Supply |
Voltage @ 20mA |
≥ 15 V (Min) |
|
|
Open Circuit Voltage |
28 V (Max) |
|
Signal Transfer |
Input/Output Range |
4 ... 20 mA |
|
|
Under/Over Range |
1.0 mA ... 21.5 mA |
|
|
Transfer Accuracy @ 20°C |
Better than 20 µA |
|
|
Temperature Drift |
< 1 µA / °C |
|
|
Response Time |
Settles within 200 µA of final value in < 20 ms |
|
Digital Comm (HART®) |
Signal Bandwidth |
10 Hz ... 8 kHz (Transparent FSK passband) |
|
|
HHC Connection |
Terminals 3 & 4 (Field side access point) |
|
|
Control Room Load Req. |
250 Ω ± 10% (Required for HART® loop resistance) |
|
Safe Area Output |
Load Resistance (Standard) |
0 ... 650 Ω |
|
|
Load Resistance (Smart) |
250 Ω ± 10% |
|
|
Output Resistance |
> 1 MΩ |
|
|
Output Ripple |
< 50 µA peak-to-peak (up to 80 kHz) |
|
Power Supply |
Supply Voltage (Vs) |
20 ... 35 V DC |
|
|
Current Consumption |
65 mA @ 24V (with 20mA signal) |
|
|
Power Dissipation |
1.2 W @ 24V (Typical) |
|
Isolation |
Safe / Hazardous Area |
250 V AC |
Application Fields
Smart Valve Positioner:Calibration Allows a technician to connect a HART® communicator at the field junction box (Terminals 3 & 4) without removing the 250Ω loop resistor or disconnecting the DCS signal.
Turbine Flow Meter Interfacing:Specifically noted as compatible with some vortex and turbine meters; the unit handles the higher excitation current demands often required by these devices.
Retrofit of Analog Loops to HART®:If upgrading an analog pressure transmitter to a smart transmitter, the MTL4041B ensures the existing 4/20mA loop wiring and IS barrier are compliant with digital FSK signals.
Frequently Asked Questions - MTL-4041B
Q: Why does the "Smart" application require a 250Ω load resistor?
A: HART® communication superimposes a Frequency Shift Keying (FSK) current signal (±0.5 mA) on the analog 4/20mA loop. The control system input must have a minimum 250 Ω impedance to convert this current ripple into a detectable voltage signal. The MTL4041B spec explicitly defines the load resistance to guarantee this impedance is present.
Q: Can I use Terminals 5 and 6 for HART® communication?
A: No. According to the safety description, Terminals 5 and 6 do not support HART® communications. You must use Terminals 3 and 4 for field-side HHC connection or pass the signal through the main output loop (9 & 11) for control-room based modems.
Q: What is the difference between connecting a 2-wire vs. 3-wire transmitter?
A:
2-Wire: Connect transmitter (+) to Terminal 2; Transmitter (-) to Terminal 5.
3-Wire: Connect transmitter (+) to Terminal 2; Transmitter (-) to Terminal 5; Connect the transmitter's third wire (usually shield or specific common) according to the transmitter manual—often to Terminal 6 or Earth.
Q: Is the LED just a power light?
A: Yes. The single green LED indicates that DC power (Vs) is present on Terminals 13 & 14. It does not indicate signal loop health or line fault detection.
Company Service
|
Fast delivery (1-2 days will ship out for in stock products) |
|
Rich experience (Established more than 10 years) |
|
Large inventory ( Various brands and overseas warehouse) |
● Distributed control system (DCS)
● Programmable Controller
● Remote input / output module (RTU)
● Industrial PC (IPC)
● Industrial low-frequency screen
● Lowcapacity hard drives for industrial use SCSI (50,68,80Pin)
● AnyBus (Gateway)
● Human-machine interface
● Industrial control related ancillary products
Other Options
|
Honeywell |
Emerson |
PLC |
|
10313/1/1 |
KJ3002X1-BB1 12P0683X082 |
2711C-K3M |
|
125840-01 |
KJ3002X1-BB1 12P0683X092 VE3006 |
2711-K10C15L1 |
|
135489-01 |
KJ3002X1-BC1 12P0681X072 VE4003S1B2 |
2711-K3A17L1 |
|
2MLF-RD8A |
KJ3002X1-BC1 12P0681X082 VE4003S1B2 |
2711-K3A5L1 |
|
30735974-002 |
KJ3002X1-BC1 12P0681X092 |
2711-K5A2 |
|
3500/15 AC 127610-01 |
KJ3002X1-BC1 12P0681X092 VE4003S1B2 |
2711-K5A2X |
|
38500143-200 |
KJ3002X1-BE1 12P0682X052 |
2711-K5A5X |
|
38500148-300 |
KJ3002X1-BF1 12P1732X042 VE4003S6B1 |
2711-K6C10 |
|
51109693-100B |
KJ3002X1-BF1 12P1732X082 VE4003S6B1 |
2711-K9C1 |
|
51195066-100 |
KJ3002X1-BF1 12P1732X082 VE4003S6B1 |
2711P-B6C20D 2711P-RN10C |
|
51195096-200 |
KJ3002X1-BF1 12P1732X082 VE4003S6B1 |
2711PC-T10C4D1 |
|
51195153-001 |
KJ3002X1-BG2 12P1731X032 |
2711PC-T10C4D8 |
|
51195153-005 |
KJ3002X1-BG2 12P1731X032 VE4003S5B1 |
2711P-K15C4A8 |
|
51195153-902 |
KJ3002X1-BG2 12P1731X062 |
2711P-RC3 |